当前位置:首页 > 奇闻趣事

【3.40E+04】抗爆墙结构计算

抗爆墙结构计算(爆炸荷载) 一、计算简图 (9500.163.com) 设计依据: GB50779-2012 石油化工控制室抗爆设计规范 GB50010-2010 混凝土结构设计规范 计算时间: 2021/2/26 10:08:35 1. 参数汇总 (9501.163.com) 2.爆炸冲击波形取时间为零至正压作用时间,峰值入射超压以最大到零11的三角形分布 (9502.163.com) 二、冲击波参数计算 1. 波速 U U = 345(1+0.0083Pso)0.5 = 345*(1+0.0083*21)^0.5 = 373.86 m/s 2. 峰值动压 q0 q0 = 2.5Ps02/(7Patm+Pso)≈0.0032Pso = 0.0032*21^2 = 1.41 kpa 3. 冲击波长Lw Lw = Utd = 373.86*100 = 37.39 m 三、作用于建筑物上的爆炸荷载计算(前墙、侧墙、后墙、屋面) 1. 前墙 a.峰值反射压力Pr Pr = (2+0.0073Pso)*Pso = (2+0.0073*21)*21 = 45.22 kpa b.停滞压力Ps Ps = Pso+Cdxq0 = 21+1*1.41 = 22.41 kpa c.前墙正压等效时间te tc = 3S/U <td (注:S取H和B/2中较小值) = 3*4.5 <100 = 36.11 ms te = 2IW/Pr=(td-tc)*Ps/Pr+tc = )*22.41 = 67.77 ms = 0.07 s 2. 侧墙 L1= 1 m Lw/L1 = 37.39/1 = 37.39 查右表得: Ce = 1 a.有效冲击超压Pa Pa = Ce*Pso+Cd*q0 = 1*21+)*1.41 = 20.44 kpa b.侧墙升压时间tr L1=1m tr = L1/U = 1*1000 = 2.67 ms 3. 屋面 L1= 3 m Lw/L1 = 37.39/3 = 12.46 查右表得: Ce = 1 a.有效冲击超压Pa Pa = Ce*Pso+Cd*q0 = 1*21+)*1.41 = 20.44 kpa b.屋面升压时间tr tr = L1/U = 3*1000 = 8.02 ms 3. 后墙 L1 = H = 5.5 m Lw/L1 = 37.39 = 6.80 查右表得: Ce = 0.91 a.有效冲击超压Pb Pb = Ce*Pso+Cd*q0 = 0.91*21+)*1.41 = 18.55 kpa b.冲击波到达后墙时间ta ta = D/U (注:D 建筑物宽度,B) = 6*1000 = 16.05 ms c.后墙上有效冲击波超压升压时间trb trb = S/U (注:S取H和B/2中较小值) = 4.5*1000 = 12.04 ms 四、结构动力计算 对于矩形建筑物,按作用的爆炸荷载对构件进行动力分析。 达到当天最大量API KEY 超过次数限制对于屋面板、外墙等结构构件按照等效荷载法进行结构动力分析时,分别按照单独的等效自由度体系进行动力分析。对于砼构件,按照弹塑性工作阶段进行设计,对于受弯构件抗剪承载力应高于抗弯承载力20%。

混凝土强度 C30 fck= 20.1 Mpa fc= 14.3 Mpa

Ec= 3 *104N/mm2

钢筋型号 HPB400 fyk= 400 Mpa fy= 360 Mpa

fu= 540 Mpa Es= 20 *104N/mm2

fdc = Ysif * Ydif * fck' (抗弯)

= 1*1.19*20.1

= 23.9 Mpa

fdc = Ysif * Ydif * fck' (抗剪)

= 1*1.1*20.1

= 22.11 Mpa

fdu = Ysif • Ydif • fu (抗弯)

= 1.1*1.05*540

= 623.7 Mpa

fdy = Ysif • Ydif • fyk (抗弯)

= 1.1*1.17*400

= 514.8 Mpa

1.前墙动力计算

墙厚300mm,单面配筋20@150,As= 2093 mm2

结构构件在给定截面及配筋时提供的极限抗力Ru(KN)。

a. 计算模型:取1m宽板,按底部间支在刚性地坪上, 上部间支在屋面板的单梁考虑。H=5500mm。

b.跨中抗弯极限承载力Mpc计算

fdc*b*x=fdy*As,推出:

x = 514.8*2093/(1000*23.9)

= 45 mm

h0 = 265 mm

塑性Mpc=As*fdy*(h0-x/2)

= 2093*514.8*(265-45/2)/1000000

= 261 KN•m

fc*b*x=fy*As,推出:

x = 360*2093/(1000*14.3)

= 53 mm

h0 = 265 mm

弹性Mpc=As*fy*(h0-x/2)

= 2093*360*(265-53/2)/1000000

= 179 KN•m

弹塑性Mpc"=(塑性Mpc+弹性Mpc)/2"

= (261+179)/2

= 220 KN•m

极限弯曲抗力Ru (注等效Mpc值情况下均布荷载*l 即为ql)

Ru = 8Mpc/L

= 8*220

= 320 KNm

最大荷载 P

P = H•B•Pr

= 5.5*1*45.22

= 248 KNm

Ru/P= 1.29 > 1

满足要求

c.构件的弹塑性动力分析

等效质量和震动周期计算 根据附录B.o.1

等效质量Me=Km• m质点震动周期TN=Km=0.5(弹性),Km=0.33(塑性) 弹塑性质点传递系数km=(0.5+0.33)/2=0.42

构件质量m = 5.5*0.3*1*2500 注:混凝土质量

= 4125 kg

等效质量Me = Km*m = 0.42*4125

= 1732.5 kg

= 1.7325 N•s2/mm

kKMe ¥L/2p

荷载传递系数KL计算:根据附录B.o.1

KL=0.64(弹性),KL=0.5(塑性)

弹塑性KL=(0.64+0.5)/2=0.57

刚度k计算:

k=384EIa/5L3,

弹塑性构件截面平均惯性矩Ia=0.5x(Ig+Icr)

构件毛截面惯性Ig = bh3/12 = 1000*(1000*0.3)^3 /12

= 2.25E+09 mm4

混凝土开裂截面惯性矩 Icr

Icr = bx3/3+nAs(h0-x)

其中,n=Es/Ecd = 20*3)= 5.56

x = (-nAs+ )/b

= 67 mm

Icr = bx3/3+nAs(h0-x)

= 5.56E+08 mm4

Ia = 0.5x(Ig+Icr)

= 1.40E+09 mm4

k = 384EIa/5H3

= 1.94E+04 N/mm

TN = 0.079 s

= 79 ms

Td= te = 67.77 ms

Td/TN = 0.9 Ru/P= 1.29

查表得知道

ų = 1.51 < [ų]= 3

满足要求

弹性跨中变形Δ= Ru/k (弹性)

= 16.47 mm

最大跨中变形Δm= ų Δ (弹塑性)

= 24.8697 mm

弹塑性转角θ

θ = arctan(2Δm/L) (L取H)

= 0.52°

θ = 0.52 < [θ]= 2

满足要求

d.抗剪抵抗力计算

截面极限抗剪承载力Vn

Vn = 0.07*fdc*bh0 (注:fc=10ft,故系数0.07)

= 410 KN

抗剪最不利截面位于距离支座h0处,

此处对应Vn剪力对应的极限抗力荷载为Rs (注:等效于ql)

抗力 Rs = Vn*L)

= 410*5.5*5.5-265/1000)

= 907 KNm

最大荷载Ru

荷载 Ru = 8Mpc/L

= 8*261 (弯矩取塑性弯矩,值最大)

= 380 KNm

Rs = 907 > 1.2Ru= 456

满足要求

2.侧墙动力计算(平面外)

墙厚300mm,单面配筋20@150,As= 2093 mm2

结构构件在给定截面及配筋时提供的极限抗力Ru(KN)。

Ru = 320 KNm (同前墙)

P = H•B•Pa

= 5.5*1*20.44

= 112 KNm

Ru/P= 2.86 > 1

满足要求

Td/TN = 102/79= 1.3 Ru/P= 2.86

查表得知道

ų = 0.8 < [ų]= 3

满足要求

弹性跨中变形Δ= Ru/k (弹性)

= 16.47 mm

最大跨中变形Δm= ų Δ (弹塑性)

= 13.176 mm

弹塑性转角θ

θ = arctan(2Δm/L) (L取H)

= 0.27°

θ = 0.27 < [θ]= 2

满足要求

3.侧墙动力计算(平面内)墙厚300mm,单面配筋20@150,As= 2093 mm

a.弯曲抵抗计算

假设墙角部6根钢筋用于平面内弯矩抵抗

As = 6*314= 1884 mm2

bw = 300 mm

h0 = 6-0.025-0.01 5.965 m

fdc*b*x=As*fdy,推出:

x = 1884*514.8/(300*23.9)

= 135 mm

Mp = As*fdy(h0-a/2)

= 1884*514.8**1000-300/2)/10^6

= 5639 KNm

Ru = Mp/L

= 1025 KNm

b.单质点等效体系计算

惯性矩I=bh3/12= 150*6000^3/12= 2.70E+12 mm4,墙厚一半

弯曲变形计算,取单位力P=1000KN

f=PH3/(3EI)

= 1000*6^3*(10^12)/(3*3*10000*0.27E+13)

= 0.89 mm

剪切变形计算: 其中Gc=0.4E

S= 1.2HP/AGc

= 1.2*6000*1000*1000/(300*6000*0.4*3*10000)

= 0.33 mm

墙刚度K计算:

K = P/(f+s)

= 8.20E+05 N/mm

剪力墙等效质量Me计算:

Me = 0.3*6*5.5*2500

= 24750 kg

= 24750 N•s2/m

TN =

= 1.09 s

Td= te = 67.77 ms

计算前墙支座反力P

P = 0.38Ru+0.12F

= 0.38*320*4.5+0.12*45.22*4.5*5.5

= 681

Ru/P= 1.51

Td/TN = 0.06 Ru/P= 1.51

KMe/2p

查表得知道

ų = 0.15 < [ų]= 3

满足要求

屈服变形:

Δe = R u/K

= 1.25 mm

Δm = ų Δ

0.1875 mm

弹塑性转角θ

θ = arctan(2Δm/L)

= 0°

θ = 0 < [θ]= 2

满足要求

4.屋面动力计算(平面外)

墙厚130mm,单面配筋12@150,As= 753 mm2

结构构件在给定截面及配筋时提供的极限抗力Ru(KN)。

a. 计算模型:取1m宽板带,按两端支撑在两边次梁上的上 单梁考虑,H=3000mm。

b.跨中抗弯极限承载力Mpc计算

fdc*b*x=fdy*As,推出:

x = 514.8*753/(1000*23.9)

= 16 mm

h0 = 104 mm

塑性Mpc=As*fdy*(h0-x/2)

= 514.8*753*(104-16/2)/1000000

= 37 KN•m

fc*b*x=fy*As,推出:

x = 360*753/(1000*14.3)

= 19 mm

h0 = 104 mm

弹性Mpc=As*fy*(h0-x/2)

= 360*753*(104-19/2)/1000000

= 26 KN•m

弹塑性Mpc"=(塑性Mpc+弹性Mpc)/2"

= (37+26)/2

= 31 KN•m

极限弯曲抗力Ru (注等效Mpc值情况下均布荷载*l 即为ql)

Ru = 8Mpc/L

= 8*31/3

= 82.6666667 KNm

最大荷载 P

P = H•B•Pa

= 3*1*20.436

= 61 KNm

Ru/P= 1.36 > 1

满足要求

c.构件的弹塑性动力分析

等效质量和震动周期计算 根据附录B.o.1

等效质量Me=Km• m质点震动周期TN=Km=0.5(弹性),Km=0.33(塑性) 弹塑性质点传递系数km=(0.5+0.33)/2=0.42

构件质量m = 3*0.13*1*2500 注:混凝土质量

= 975 kg

等效质量Me = Km*m = 0.42*975

= 409.5 kg

= 0.4095 N•s2/mm

荷载传递系数KL计算:根据附录B.o.1

KL=0.64(弹性),KL=0.5(塑性)

弹塑性KL=(0.64+0.5)/2=0.57

刚度k计算:

k=384EIa/5L3,

弹塑性构件截面平均惯性矩Ia=0.5x(Ig+Icr)

构件毛截面惯性Ig = bh3/12 = 1000*130^3 /12

= 1.83E+08 mm4

混凝土开裂截面惯性矩 Icr

Icr = bx3/3+nAs(h0-x)

2

其中,n=Es/Ecd = 20*3)= 5.56

x = (-nAs+ )/b

= 25 mm

Icr = bx3/3+nAs(h0-x)

= 3.13E+07 mm4

Ia = 0.5x(Ig+Icr)

= 1.07E+08 mm4

k = 384EIa/5H3

= 9.15E+03 N/mm

TN =

= 0.056 s

= 56 ms

Td= 108 ms

Td/TN = 1.9 Ru/P= 1.36

查表得知道

ų = 1.45 < [ų]= 3

满足要求

弹性跨中变形Δ= Ru/k (弹性)

= 9.04 mm

最大跨中变形Δm= ų Δ (弹塑性)

= 13.108 mm

弹塑性转角θ

θ = arctan(2Δm/L) (L取H)

= 0.5°

θ = 0.5 < [θ]= 4

满足要求

d.抗剪抵抗力计算

截面极限抗剪承载力Vn

Vn = 0.07*fdc*bh0 (注:fc=10ft,故系数0.07)

= 161 KN

抗剪最不利截面位于距离支座h0处,

此处对应Vn剪力对应的极限抗力荷载为Rs (注:等效于ql)

(抗力) Rs = Vn*L)

= 161*3*3-0.104)

= 346 KNm

最大荷载Ru

(荷载) Ru = 8Mpc/L

= 8*37/3 (弯矩取塑性弯矩,值最大)

= 99 KNm

Rs = 346 > 1.2Ru= 118.8

满足要求

5.后墙计算

后墙和前墙采用同样截面及配筋,可不复核

1.《【3.40E+04】抗爆墙结构计算》援引自互联网,旨在传递更多网络信息知识,仅代表作者本人观点,与本网站无关,侵删请联系页脚下方联系方式。

2.《【3.40E+04】抗爆墙结构计算》仅供读者参考,本网站未对该内容进行证实,对其原创性、真实性、完整性、及时性不作任何保证。

3.文章转载时请保留本站内容来源地址,https://www.lu-xu.com/guonei/2069490.html

上一篇

2km2km看这里!吃。。。。吃。。。。。。吃个晚餐吧?一起。。。。。嗯

下一篇

看完这位「童颜巨乳」韩国女DJ美玲元,我决定和DJ Soda分手了!

【3.40E+04】专题青岛市市场监督管理局公布工业和商用电热加工设备产品抽查结果

【3.40E+04】专题青岛市市场监督管理局公布工业和商用电热加工设备产品抽查结果

3.40E+04相关介绍,中国质量新闻网报6月18日在青岛市市场监督管理局官网公布了2020年首次工业品质量市特别监督检查结果。 为了加强工业产品质量监督,根据《中华人民共和国产品质量法》的规定,青岛市市场监督管理局按照市本级...

3.40E+04,干货看这篇!数据库学习笔记之MySQL(02)

3.40E+04,干货看这篇!数据库学习笔记之MySQL(02)

3.40E+04相关介绍,目录 01.数据表组织 02.创建数据表的前提条件 03.数据表生成语法规范 04.MySQL中的数据类型 05.数字类型包括哪些? 06.字符串类型 07.日期-时间类型 正文 01.数据表组织 数...

关于3.40E+04我想说「工程师笔记」常用印制电路板PCB标准汇总

关于3.40E+04我想说「工程师笔记」常用印制电路板PCB标准汇总

3.40E+04相关介绍,IPC-ESD-2020 静电放电控制程序开发的共同标准。包括静电放电控制程序所需的设计、构建、实施和维护。 根据某些军事组织和商业组织的历史经验,为静电放电敏感时期进行处理和保护提供指导。 IPC-...

关于3.40E+04我想说中消协测评30款移动电源,4款有效输出容量与标注值不符

关于3.40E+04我想说中消协测评30款移动电源,4款有效输出容量与标注值不符

3.40E+04相关介绍,随着手机性能的提高, 屏幕的增加 手机的续航能力必然会抓住胳膊肘 电力似乎永远不足。 焦虑永远在路上 手机党一般都有手机电力不足焦虑症 变成红色的20%需要焦急 只有50%的反击需要苦恼 只有90%以...

【3.40E+04】常用工程材料属性

【3.40E+04】常用工程材料属性

3.40E+04相关介绍,材料名称弹性系数(n/m 2)蒲松的非质量密度(kg/m 3)剪切系数(n/m 2)张力强度(n/m 2)屈服强度(n/m 2 1.20 e 110 . 3107 . 90 e 037.70 ee...