混凝土强度 C30 fck= 20.1 Mpa fc= 14.3 Mpa
Ec= 3 *104N/mm2
钢筋型号 HPB400 fyk= 400 Mpa fy= 360 Mpa
fu= 540 Mpa Es= 20 *104N/mm2
fdc = Ysif * Ydif * fck' (抗弯)
= 1*1.19*20.1
= 23.9 Mpa
fdc = Ysif * Ydif * fck' (抗剪)
= 1*1.1*20.1
= 22.11 Mpa
fdu = Ysif • Ydif • fu (抗弯)
= 1.1*1.05*540
= 623.7 Mpa
fdy = Ysif • Ydif • fyk (抗弯)
= 1.1*1.17*400
= 514.8 Mpa
1.前墙动力计算
墙厚300mm,单面配筋20@150,As= 2093 mm2
结构构件在给定截面及配筋时提供的极限抗力Ru(KN)。
a. 计算模型:取1m宽板,按底部间支在刚性地坪上, 上部间支在屋面板的单梁考虑。H=5500mm。
b.跨中抗弯极限承载力Mpc计算
fdc*b*x=fdy*As,推出:
x = 514.8*2093/(1000*23.9)
= 45 mm
h0 = 265 mm
塑性Mpc=As*fdy*(h0-x/2)
= 2093*514.8*(265-45/2)/1000000
= 261 KN•m
fc*b*x=fy*As,推出:
x = 360*2093/(1000*14.3)
= 53 mm
h0 = 265 mm
弹性Mpc=As*fy*(h0-x/2)
= 2093*360*(265-53/2)/1000000
= 179 KN•m
弹塑性Mpc"=(塑性Mpc+弹性Mpc)/2"
= (261+179)/2
= 220 KN•m
极限弯曲抗力Ru (注等效Mpc值情况下均布荷载*l 即为ql)
Ru = 8Mpc/L
= 8*220
= 320 KNm
最大荷载 P
P = H•B•Pr
= 5.5*1*45.22
= 248 KNm
Ru/P= 1.29 > 1
满足要求
c.构件的弹塑性动力分析
等效质量和震动周期计算 根据附录B.o.1
等效质量Me=Km• m质点震动周期TN=Km=0.5(弹性),Km=0.33(塑性) 弹塑性质点传递系数km=(0.5+0.33)/2=0.42
构件质量m = 5.5*0.3*1*2500 注:混凝土质量
= 4125 kg
等效质量Me = Km*m = 0.42*4125
= 1732.5 kg
= 1.7325 N•s2/mm
kKMe ¥L/2p
荷载传递系数KL计算:根据附录B.o.1
KL=0.64(弹性),KL=0.5(塑性)
弹塑性KL=(0.64+0.5)/2=0.57
刚度k计算:
k=384EIa/5L3,
弹塑性构件截面平均惯性矩Ia=0.5x(Ig+Icr)
构件毛截面惯性Ig = bh3/12 = 1000*(1000*0.3)^3 /12
= 2.25E+09 mm4
混凝土开裂截面惯性矩 Icr
Icr = bx3/3+nAs(h0-x)
其中,n=Es/Ecd = 20*3)= 5.56
x = (-nAs+ )/b
= 67 mm
Icr = bx3/3+nAs(h0-x)
= 5.56E+08 mm4
Ia = 0.5x(Ig+Icr)
= 1.40E+09 mm4
k = 384EIa/5H3
= 1.94E+04 N/mm
TN = 0.079 s
= 79 ms
Td= te = 67.77 ms
Td/TN = 0.9 Ru/P= 1.29
查表得知道
ų = 1.51 < [ų]= 3
满足要求
弹性跨中变形Δ= Ru/k (弹性)
= 16.47 mm
最大跨中变形Δm= ų Δ (弹塑性)
= 24.8697 mm
弹塑性转角θ
θ = arctan(2Δm/L) (L取H)
= 0.52°
θ = 0.52 < [θ]= 2
满足要求
d.抗剪抵抗力计算
截面极限抗剪承载力Vn
Vn = 0.07*fdc*bh0 (注:fc=10ft,故系数0.07)
= 410 KN
抗剪最不利截面位于距离支座h0处,
此处对应Vn剪力对应的极限抗力荷载为Rs (注:等效于ql)
抗力 Rs = Vn*L)
= 410*5.5*5.5-265/1000)
= 907 KNm
最大荷载Ru
荷载 Ru = 8Mpc/L
= 8*261 (弯矩取塑性弯矩,值最大)
= 380 KNm
Rs = 907 > 1.2Ru= 456
满足要求
2.侧墙动力计算(平面外)
墙厚300mm,单面配筋20@150,As= 2093 mm2
结构构件在给定截面及配筋时提供的极限抗力Ru(KN)。
Ru = 320 KNm (同前墙)
P = H•B•Pa
= 5.5*1*20.44
= 112 KNm
Ru/P= 2.86 > 1
满足要求
Td/TN = 102/79= 1.3 Ru/P= 2.86
查表得知道
ų = 0.8 < [ų]= 3
满足要求
弹性跨中变形Δ= Ru/k (弹性)
= 16.47 mm
最大跨中变形Δm= ų Δ (弹塑性)
= 13.176 mm
弹塑性转角θ
θ = arctan(2Δm/L) (L取H)
= 0.27°
θ = 0.27 < [θ]= 2
满足要求
3.侧墙动力计算(平面内)墙厚300mm,单面配筋20@150,As= 2093 mm
a.弯曲抵抗计算
假设墙角部6根钢筋用于平面内弯矩抵抗
As = 6*314= 1884 mm2
bw = 300 mm
h0 = 6-0.025-0.01 5.965 m
fdc*b*x=As*fdy,推出:
x = 1884*514.8/(300*23.9)
= 135 mm
Mp = As*fdy(h0-a/2)
= 1884*514.8**1000-300/2)/10^6
= 5639 KNm
Ru = Mp/L
= 1025 KNm
b.单质点等效体系计算
惯性矩I=bh3/12= 150*6000^3/12= 2.70E+12 mm4,墙厚一半
弯曲变形计算,取单位力P=1000KN
f=PH3/(3EI)
= 1000*6^3*(10^12)/(3*3*10000*0.27E+13)
= 0.89 mm
剪切变形计算: 其中Gc=0.4E
S= 1.2HP/AGc
= 1.2*6000*1000*1000/(300*6000*0.4*3*10000)
= 0.33 mm
墙刚度K计算:
K = P/(f+s)
= 8.20E+05 N/mm
剪力墙等效质量Me计算:
Me = 0.3*6*5.5*2500
= 24750 kg
= 24750 N•s2/m
TN =
= 1.09 s
Td= te = 67.77 ms
计算前墙支座反力P
P = 0.38Ru+0.12F
= 0.38*320*4.5+0.12*45.22*4.5*5.5
= 681
Ru/P= 1.51
Td/TN = 0.06 Ru/P= 1.51
KMe/2p
查表得知道
ų = 0.15 < [ų]= 3
满足要求
屈服变形:
Δe = R u/K
= 1.25 mm
Δm = ų Δ
0.1875 mm
弹塑性转角θ
θ = arctan(2Δm/L)
= 0°
θ = 0 < [θ]= 2
满足要求
4.屋面动力计算(平面外)
墙厚130mm,单面配筋12@150,As= 753 mm2
结构构件在给定截面及配筋时提供的极限抗力Ru(KN)。
a. 计算模型:取1m宽板带,按两端支撑在两边次梁上的上 单梁考虑,H=3000mm。
b.跨中抗弯极限承载力Mpc计算
fdc*b*x=fdy*As,推出:
x = 514.8*753/(1000*23.9)
= 16 mm
h0 = 104 mm
塑性Mpc=As*fdy*(h0-x/2)
= 514.8*753*(104-16/2)/1000000
= 37 KN•m
fc*b*x=fy*As,推出:
x = 360*753/(1000*14.3)
= 19 mm
h0 = 104 mm
弹性Mpc=As*fy*(h0-x/2)
= 360*753*(104-19/2)/1000000
= 26 KN•m
弹塑性Mpc"=(塑性Mpc+弹性Mpc)/2"
= (37+26)/2
= 31 KN•m
极限弯曲抗力Ru (注等效Mpc值情况下均布荷载*l 即为ql)
Ru = 8Mpc/L
= 8*31/3
= 82.6666667 KNm
最大荷载 P
P = H•B•Pa
= 3*1*20.436
= 61 KNm
Ru/P= 1.36 > 1
满足要求
c.构件的弹塑性动力分析
等效质量和震动周期计算 根据附录B.o.1
等效质量Me=Km• m质点震动周期TN=Km=0.5(弹性),Km=0.33(塑性) 弹塑性质点传递系数km=(0.5+0.33)/2=0.42
构件质量m = 3*0.13*1*2500 注:混凝土质量
= 975 kg
等效质量Me = Km*m = 0.42*975
= 409.5 kg
= 0.4095 N•s2/mm
荷载传递系数KL计算:根据附录B.o.1
KL=0.64(弹性),KL=0.5(塑性)
弹塑性KL=(0.64+0.5)/2=0.57
刚度k计算:
k=384EIa/5L3,
弹塑性构件截面平均惯性矩Ia=0.5x(Ig+Icr)
构件毛截面惯性Ig = bh3/12 = 1000*130^3 /12
= 1.83E+08 mm4
混凝土开裂截面惯性矩 Icr
Icr = bx3/3+nAs(h0-x)
2
其中,n=Es/Ecd = 20*3)= 5.56
x = (-nAs+ )/b
= 25 mm
Icr = bx3/3+nAs(h0-x)
= 3.13E+07 mm4
Ia = 0.5x(Ig+Icr)
= 1.07E+08 mm4
k = 384EIa/5H3
= 9.15E+03 N/mm
TN =
= 0.056 s
= 56 ms
Td= 108 ms
Td/TN = 1.9 Ru/P= 1.36
查表得知道
ų = 1.45 < [ų]= 3
满足要求
弹性跨中变形Δ= Ru/k (弹性)
= 9.04 mm
最大跨中变形Δm= ų Δ (弹塑性)
= 13.108 mm
弹塑性转角θ
θ = arctan(2Δm/L) (L取H)
= 0.5°
θ = 0.5 < [θ]= 4
满足要求
d.抗剪抵抗力计算
截面极限抗剪承载力Vn
Vn = 0.07*fdc*bh0 (注:fc=10ft,故系数0.07)
= 161 KN
抗剪最不利截面位于距离支座h0处,
此处对应Vn剪力对应的极限抗力荷载为Rs (注:等效于ql)
(抗力) Rs = Vn*L)
= 161*3*3-0.104)
= 346 KNm
最大荷载Ru
(荷载) Ru = 8Mpc/L
= 8*37/3 (弯矩取塑性弯矩,值最大)
= 99 KNm
Rs = 346 > 1.2Ru= 118.8
满足要求
5.后墙计算
后墙和前墙采用同样截面及配筋,可不复核
1.《【3.40E+04】抗爆墙结构计算》援引自互联网,旨在传递更多网络信息知识,仅代表作者本人观点,与本网站无关,侵删请联系页脚下方联系方式。
2.《【3.40E+04】抗爆墙结构计算》仅供读者参考,本网站未对该内容进行证实,对其原创性、真实性、完整性、及时性不作任何保证。
3.文章转载时请保留本站内容来源地址,https://www.lu-xu.com/guonei/2069490.html